background image

2 / 4 

 

P/N 387021P-

EN • REV 12 • ISS 23JUL13

 

Figure 1: Mounting the SIGA-CT1 module 

 

(1)  Compatible electrical box 

(2)  SIGA-CT1 module 

(3)  Wall plate, white (single-gang) 

  (4)  #6-32 × 5/8 in. (16 mm) screw 

(5)  #4 × 1/2 in. (13 mm) screw 

 

Wiring 

Wire in accordance with applicable requirements of the latest 

editions of the local codes and 

standards and the local 

authority having jurisdiction. 

Note: 

When stripping wire ends, exposing more wire may 

cause a ground fault; exposing less wire may result in a faulty 

connection. 

To wire the module: 

1. 

Verify that all field wiring is free of opens, shorts, and 

ground faults.

 

2. 

Strip 1/4 in. (about 6 mm) from the ends of all wires that 

connect to the terminal block of the module.

 

3.  Make all wiring connections as shown in Figure 2. 

Notes 

 

Refer to the Signature loop controller installation sheet for 

SLC wiring specifications for additional details.

 

 

All wiring is power-limited and supervised. 

 

A test resistor is supplied with the SIGA-CT1 to prevent 

trouble signals on unused circuits during installation. 

When connecting field wires, remove the test resistors and 

install a UL/ULC Listed 47 KΩ EOLR at the end of the 

circuit. 

Figure 2: Wiring diagram 

 

(1) 

EOL resistor (PN EOL

-47) 

(2) 

22 kΩ resistor

 

for 

use with 

personality code 18 

(3)  Typical NO initiating device 

(4) 

Max. 10 VDC @ 350 µA

 

(5) 

Red LED (alarm/active)

 

  (6) 

Green LED (normal)

 

(7) 

Signaling line circuit (from 

previous device) 

(8)  Signaling line circuit (to next 

device) 

Specifications 

 
Operating voltage 

15.20 to 19.95 VDC

 

Current 

 

Standby 

 

Activated 

 

300 

µ

450 µA

 

Ground fault impedance

 

10 kΩ

 

Initiating device circuit (IDC) 

 

EOL resistor value

 

 

Circuit resistance  

 

Circuit capacitance 

 

47 kΩ, UL/ULC Listed

 

50 Ω (25 Ω per wire), max.

 

0.1 

µ

F max. 

Circuit designation 

 

Signaling line circuit 

 

Notification line circuit

 

 

Class A, Style 6 or Class B, Style 4 

Class B, Style B 

Wire sizes 

12 to 18 AWG wire (0.75 to 2.5 mm²) 

Compatible electrical boxes 

2-1/2 in. (64 mm) deep single-gang 

box; 4-in. square box 1-1/2 in (38 mm) 

deep with single-gang cover 

LPCB/CPD electrical box

 

 

Requirements

 

 

 

Minimum (W × H × D) 

 

Plastic box with cover plate, no gaps or 

unused holes 

2.4 × 3.5 × 1.5 in. (60 × 85 × 38 mm) 

Operating environment 

 

Temperature 

 

Relative humidity

 

 

32 to 120°F (0 to 49°C) 

0 to 93%, noncondensing 

Storage temperature range 

−4 to 140°F (−20 to 60°C)

 

(1)

(2)

(3)

(4)

(4)

(5)

7

8

1

2

3

4

 +

 +

 –

 –

(1)

(3)

(4)

(6)

(8)

(7)

(5)

(2)

(4)

(1)

(3)