background image

 3 

The PD66 and PD620 are designed for use on Three Phase (3Ø) WYE 120/ 
208V 4-pole 5-wire electrical service. With the ability to operate on Single 

Phase (1Ø) 120/240V 3-pole 4-wire electrical service, (easily configured 

internally). 
 

DO NOT connect high voltage leg of DELTA type systems (the higher voltage 
will damage sensitive equipment connected this way)—see NOTE below. 
 

The 

PD66 

can provide up to 140 amps total, 40 amps on one leg, 50 amps 

each on remaining two legs (3Ø WYE 120/208V hook-up), 

OR 

*70 amps per 

leg (two legs) (1Ø 120/240V hook-up <internal configuration>). 
 
The 

PD620 

can provide up to 120 amps total, 40 amps per leg (three legs) 

(3Ø WYE 120/208V hook-up), 

OR 

*60 amps per leg (two legs) (1Ø 120/240V 

hook-up <internal configuration>). 

 

* When using Single Phase, incoming supply lines MUST be sized to accomodate 
20 amps more per leg than highest per leg rating (PD66-70 amps, PD620-60 

amps). 

NOTE: 

Delta systems have one (1) leg at a higher potential (208 Volts) in reference 

to neutral, sometimes termed “Crazy Leg”, or “High Leg” typically the orange color 

is reserved for designation of this line.  

Do not 

conect this leg into the 

PD66 or PD 620. 

Reviews: