Installation
Concluding activities
17
Connecting the flue pipe from the precipitator to
the chimney
The flue pipe (flue tube) from the precipitator to the
chimney must be connected on site. See the technical
data for the required dimensions; see chapter
. Easily accessible cleaning openings
must be available in the flue pipe.
Establish earthing between the precipitator and
flue pipe to the chimney
Additional earthing should be established between the
precipitator and the flue pipe to the chimney (flue tube)
to prevent the flue tube from being charged.
A perforated tape that attaches to the precipitator flue
gas connection and the flue tube is best suited.
Fig. 5-11: Additional earthing
Insulate the connecting pipe to the chimney
The connection between the boiler and the chimney
should be insulated with at least 30 mm, preferably 50
mm, of mineral wool to avoid thermal losses, which
can lead to a build-up of condensation.