www.eta.co.at
Electrical connection
Electrical connections
Guide the line from the precipitator to the circuit board
[HA-C]. Attach the 3 pole plug to [S51]. Attach the
individual wires (brown) to [S53] on the "COM" contact.
Connect the previously disconnected 3 pole plug with
the 3 pole socket. Now attach the previously detached
wire from the "COM" contact to the screw terminal.
Also attach the CAN-Bus to the circuit board [HA-C], or
if it is occupied, to another open CAN-Bus terminal.
A terminal resistor (yellow jumper) must be set at
the end of the CAN-Bus . If both CAN-Bus
terminals are allocated, the terminal resistor must be
removed on this circuit board.
In the example listed above, the terminal resistor must
be removed from the circuit board [HA-C] at [X49].
Check the node numbers if the circuit boards are
the same design.
If multiple circuit boards of the same design (e.g.: 2x
EM-C) are connected to one another via CAN-bus, the
circuit boards of the same design must have serial
node numbers. In this way they are recognized in
CAN-bus and can be configured.