Cleaning and maintenance
Cleaning (customer)
21
CAUTION!
Do not lubricate the washer and sealing area
Never lubricate the sealing area in the flue
duct or the washer on the air valve with oil,
grease or other lubricants. The reason for
this is because dust particles in the flue gas
adhere to the lubricant and cause encrustation and
sluggishness.
Check if the seal on the cover is intact and replace if
necessary.
Fig. 2-33: Seal
Re-install the actuator. Tighten the screws alternately
and evenly.
Fig. 2-34: Actuator
Removing the maintenance cover
Remove the insulation above the maintenance cover.
Fig. 2-35: Insulation
Remove the maintenance cover.
Fig. 2-36: Maintenance cover
Cleaning the inner walls of the flue gas duct
Clean the insides of the flue gas duct with the cleaning
brush. Allow the ash to fall down.
Fig. 2-37: Flue gas duct