Maintenance (expert)
Cleaning and maintenance
If resistance is noticeable when blowing out,
remove the cover on the front side (see the
following diagram) and clean the connection for the
silicone hose behind it.
Fig. 2-82: Cover
Calibrate the vacuum sensor
With the boiler switched off and silicone hose
removed, the control system must display a measured
value of 0 Pa. This measured value can be seen with
the [Service] authorisation in the text menu under:
If a different value is shown, a calibration using the
[Offset] parameter must be carried out.
For this parameter, enter the difference from the target
value of 0 Pa. Example:
Negative-pressure = 2 Pa => Offset = -2
Reconnecting the silicone hose
Reconnect the silicon hose to the vacuum actuator.
Ensure the correct position when connecting. The
silicon hose may not be kinked.
Fig. 2-83: Silicon hose
Mounting the cover on the front
Mount the cover on the front of the boiler.
Fig. 2-84: Cover