Heating water
Refilling
91
Complete desalination not required
If there is no aluminium (heat exchanger in the gas
boiler or aluminium radiator) in the system, then costly
complete desalination with ion exchange cartridges or
osmosis is not required.
Lime stabilisation can be dangerous
The addition of lime stabilising agents prevents
limescale. However, we advise against doing this.
These agents increase the salt content and result in an
undefined pH value. If the system is filled with large
amounts of water, exactly the same agent must be
used again. Mixing with other water additives or with
antifreeze can result in corrosion.
12.2
Refilling
Fill up heating water
If water refilling in the heating system is required, for
example to adjust the pressure, the same water as
used during initial filling should be used wherever
possible.
If only a small amount of water is to be replenished
(below 10% the system volume), then normal tap
water can be used. This applies, for example, when
replacing a pump or mixer.
The heating system is never to be refilled with
rainwater, as this is usually contaminated and the
pH value is too low.
Summary of Contents for HACK 20
Page 1: ...2017 01 30 EN 0000000294 V 003 2 38 0 3005 3106 93526 001 Wood chip boiler 20 90 kW Operation ...
Page 15: ...Changing the fuel Settings 15 4 2 Settings ...
Page 35: ...ETAtouch controller Boiler function block HACK 35 ...
Page 45: ...ETAtouch controller Buffer function block 45 ...
Page 49: ...ETAtouch controller Hot water tank function block 49 ...
Page 53: ...ETAtouch controller Fresh water module function block 53 ...
Page 67: ...ETAtouch controller Solar function block 67 ...
Page 73: ...ETAtouch controller Heating pipeline function block 73 ...
Page 92: ...www eta co at www eta co at downloads DOWNLOAD ...