Setting the pump
Commissioning
7.2
Setting the pump
Operating modes of the pump
1
Operation: differential pressure variable (Δp-v)
2
Operation: differential pressure constant (Δp-c)
3
Operation: constant speed
4
Operating phase
5
Operating button for setting the operating mode
and operating phase
Differential pressure variable (Δp-v)
•
The differential pressure target value "H" is
increased linearly from "½ H" to "H" over the flow
rate "Q." The differential pressure produced by the
pump is set to the respective differential pres-
sure target value.
This operating mode is recommended for
radiators for reducing flow noises on the
thermostat valves.
Differential pressure constant (Δp-c)
•
The differential pressure is held constant at the set
differential pressure target value "H".
This operating mode is recommended for
underfloor heating, large pipelines and all ap-
plications without a changeable piping characteris-
tic curve (e.g. hot water, charging pumps).