ETAtouch controller
Software version X.36.0 and later
25
secondary pump starts once the primary side reaches
45 °C (= 50° - 5 °C).
If 45 °C has not been achieved before the lapse of the
set duration [Sec. pump max. switch-on delay], the
secondary pump still starts up in order to supply the
consumer.
The secondary pump is switched off when the
consumer's demand has been met.
A maximum flow temperature can be set for the
secondary side in order to protect the underfloor
heating, for example. Underfloor heating and
wall heating systems still require a safety thermostat,
however.