Automatic operation
4
Automatic operation
Automatic operation with the pellet burner
If the buffer is empty and the log boiler is not delivering
any more heat, a green LED on the digital room sensor
(optional accessory) indicates that fuel replenishment
is needed. If no additional logs are added within the
selected time (factory setting 10 minutes, see
9.3.2.1
"Start lag"
for adjustment) the pellet burner will start au-
tomatically and take care of heating. Therefore, it is not
necessary to manually switch between log and pellet
modes.
If the insulating door of the log boiler stays open
longer than 1 minute, the ETAtouch control
system will automatically switch the pellet burner off on
the assumption that the log boiler will be started.
When the insulation door is opened, the draught fan
starts and a message appears on the display.
However, if no logs are added and ignited, the draught
fan will switch back off after 30 minutes. Then the
ETAtouch control system will restart the pellet burner
as needed.
If no logs are added, the log boiler can also be
switched off in its function block with the
switch after the log boiler's insulation door has been
closed. The waiting period of 30 minutes will then be
skipped and the control system can start the pellet
burner immediately.
Only add wood if the log boiler will immediately
take over heating operations.
WARNING!
Wood may only be added to the log boiler if it will
then be heated up, i.e. take over heating
operations.
Otherwise, if the pellet burner is switched on, there is
a risk that it will switch on when there is a request from
the buffer. The flames cause the wood to release gas.
This gas will not be fully combusted and can lead to tar
build-up in the boiler and explosions.
Buffer switch on/off temperatures
In the buffer's function block you can set a minimum
temperature for the upper buffer section (=[Buffer top
min.], see
9.4.4.1 "Buffer top min."
) which the buffer
storage tank will maintain. There is also a switch-off
temperature (=[Buffer bottom off], see
9.4.4.2 "Buffer
bottom off"
) which specifies when the boiler stops
charging the buffer.
The buffer's adjustable charging times (see
9.4.1
"Setting the buffer charging times"
) define when the
buffer can request heat from the boiler. If the log boiler
does not supply this heat, the pellet burner will be
started.
In other words, if temperature [Buffer top min.] or
function [Full buffer charge with pellets] are set to
[Yes], the buffer will be kept at temperature continually
and the charging status will be correspondingly high.
Therefore, for heating mode with the log boiler,
the charging status of the buffer must be checked
before heating up. The addition of too much wood
must be avoided to prevent overheating. The correct
amount of wood is indicated in table
7 "Correct quantity
of wood"
.
Summary of Contents for TWIN 20 kW
Page 1: ...2016 04 02 EN 0000000302 V 001 X 36 0 2303 93412 001 TWIN pellet burner 20 26 kW Operation ...
Page 39: ...ETAtouch controller TWIN function block 39 ...
Page 49: ...ETAtouch controller Buffer function block 49 ...
Page 53: ...ETAtouch controller Hot water tank function block 53 ...
Page 57: ...ETAtouch controller Fresh water module function block 57 ...
Page 81: ......
Page 82: ...www eta co at ...
Page 83: ......
Page 84: ...www eta co at ...