ETAtouch controller
[Heating circuit] function block
65
9.7.4
Text menu - Adjustable parameters
9.7.4.1
Room effect
Explanation of [Room effect]
Optional: only for room sensor
The flow temperature is calculated on the basis of the
heating curve and the outside temperature. If the room
temperature falls by 1°C, the target flow temperature is
increased by this set value. If the room temperature
rises by 1°C, the target flow temperature is decreased
by the set value.
For underfloor and wall heating with a design
temperature of 30 °C, set the room influence to 1
°C; with a design temperature of 40 °C, set it to 2 °C.
The [Service] access level is required to perform
modifications.
The parameter can be found under:
9.7.4.2
Switch-on diff. room and Switch-off
diff. room
Explanation of [Switch-on diff. room] and [Switch-
off diff. room]
Optional: only for room sensor
These parameters specify the allowed deviation of the
set room temperature for switching the heating circuit
on and off.
Example:
Room temperature setting = 21 °C
[Switch-on diff. room] = 0.5 °C
[Switch-off diff. room] = 2 °C
=> The heating circuit will be switched off as soon as
the room temperature reaches 23 °C (=21 + 2 °C). If
the room temperature falls to 21.5 °C (=21+0.5 °C),
heat is supplied to the heating circuit again.
The [Service] access level is required to perform
modifications.
The parameter can be found under:
Heating circuit
Room
Room effect
Heating circuit
Room
Switch-on diff. room
Switch-off diff. room
Summary of Contents for TWIN 20 kW
Page 1: ...2016 04 02 EN 0000000302 V 001 X 36 0 2303 93412 001 TWIN pellet burner 20 26 kW Operation ...
Page 39: ...ETAtouch controller TWIN function block 39 ...
Page 49: ...ETAtouch controller Buffer function block 49 ...
Page 53: ...ETAtouch controller Hot water tank function block 53 ...
Page 57: ...ETAtouch controller Fresh water module function block 57 ...
Page 81: ......
Page 82: ...www eta co at ...
Page 83: ......
Page 84: ...www eta co at ...