[Solar] function block
ETAtouch controller
If one of the described conditions is not met (for
example, if the buffer is currently being charged
by the boiler), there is no reason to feed the solar
charge to the upper buffer coil. Therefore, the solar
charge is directed into the lower coil in order to charge
this area. If all conditions are once again met, charging
is switched to the upper coil.
The only exception to this is when solar power
increases while charging the lower buffer coil.
Then, once the minimum time (factory setting 20 min.)
passes, charging will switch to the upper coil, although
the conditions are not met.
9.8.4
Solar heating system with external
heat exchanger
Solar heating system with external heat exchanger
The control principle is the same as in a solar heating
system with just one tank, see chapter
9.8.1 "Solar
heating system with one tank"
.
The speed of the collector pump also controls the
adjustable temperature difference [Target collector
diff.] between the collector and the tank.
Fig. 9-60: Solar heating system with external heat exchanger
connected to buffer
In addition, a variable speed secondary pump is
available for the heat exchanger. Through speed
adjustment, it attempts to adapt the temperature
difference between collector and secondary flow (see
chart 78 °C - 74°C = 4 °C) to the temperature
difference between the return of the solar heating
system and the tank (49 °C - 45 °C = 4 °C).
Fig. 9-61: Regulation principle
Summary of Contents for TWIN 20 kW
Page 1: ...2016 04 02 EN 0000000302 V 001 X 36 0 2303 93412 001 TWIN pellet burner 20 26 kW Operation ...
Page 39: ...ETAtouch controller TWIN function block 39 ...
Page 49: ...ETAtouch controller Buffer function block 49 ...
Page 53: ...ETAtouch controller Hot water tank function block 53 ...
Page 57: ...ETAtouch controller Fresh water module function block 57 ...
Page 81: ......
Page 82: ...www eta co at ...
Page 83: ......
Page 84: ...www eta co at ...