Prepare to Install
13
• Sensor IQ models can be flush-mounted under certain conditions:
- The 120 V 12-breaker and 24-breaker panels can be flush-mounted between studs; assuming
8.9 cm (3.5 in) stud depth with 1.3 cm (1/2 in) surfacing material and studs are on
40.6 cm (16 in) centers.
- The 120 V 48-breaker panel, 240 V panel, and 277 V panel can be flush-mounted if there is
deeper wall construction (e.g., 2 in x 6 in) with custom framing to accommodate the additional
depth and width of the panel.
• The installation location must support a fully populated and wired Sensor IQ Breaker Panel, not
exceeding 54.5 kg (120 lb).
• The US National Electric Code requires that the highest circuit breaker be located no more than
2 m (6 ft 7 in) off the floor.
Electrical Input Requirements
• Refer to
for information on mains feed for each Sensor IQ Breaker
Panel model.
• This equipment must be connected to a suitable safety earth/ground.
Clearance
• Sensor IQ doors can be mounted to open from the left or the right.
• Allow clearances as described below.
.
Note:
The maximum weight, 54.5 kg (120 lb), includes a fully populated breaker panel and
does not include the weight of conduit, wiring, or options (e.g., main breakers, fuses,
etc.).
120 V Sensor IQ Panel Dimensions
Model
Height
Width
Depth
12 breaker - no main breaker
panel only
0.87 m (34.25 in)
0.362 m (14.25 in) 10.2 cm (4 in)
12 breaker - with main breaker
panel only
1.022 m (40.25 in)
0.362 m (14.25 in) 10.2 cm (4 in)
12 breaker - no main breaker
with recess mounted door
0.914 m (36 in)
0.406 m (16 in)
12.0 cm (4.75 in)
12 breaker - with main breaker
with recess mounted door
1.066 m (42 in)
0.406 m (16 in)
12.0 cm (4.75 in)
12 breaker - no main breaker
with surface mount door
0.87 m (34.25 in)
0.362 m (14.25 in) 12.0 cm (4.75 in)
12 breaker - with main breaker
with surface mount door
1.022 m (40.25 in)
0.362 m (14.25 in) 12.0 cm (4.75 in)
24 breaker
panel only
1.276 m (50.25 in)
0.362 m (14.25 in) 10.2 cm (4 in)
24 breaker
with recess mount door
1.321 m (52 in)
0.406 m (16 in)
12.0 cm (4.75 in)
24 breaker
with surface mount door
1.276 m (50.25 in)
0.362 m (14.25 in) 12.0 cm (4.75 in)
48 breaker
panel only
1.626 m (64 in)
0.508 m (20 in)
13.3 cm (5.25 in)
48 breaker
with recess mount door
1.676 m (66 in)
0.559 m (22 in)
15.2 cm (6 in)
48 breaker
with surface mount door
1.626 m (64 in)
0.508 m (20 in)
15.2 cm (6 in)