Installation
31
*See the white paper
Understanding 0-10V LED Drivers
for Class 2 and Class 1 wiring considerations.
Primary/Secondary Switch (IQ48 only)
When using any combination of two 0–10V, DALI, or
Contact Input option cards in a Sensor IQ you will need to
position the Primary/Secondary switch prior to startup. The
Primary/Secondary switch controls which set of breakers
responds to each option card.
Option Card 1 will always control circuits 1–24. If the
Primary/Secondary switch is in the “OFF” position, Option
Card 2 will also control circuits 1–24. If the Primary/
Secondary switch is in the “ON” position, Option Card 2 will
control circuits 25–48. See the examples in the tables below.
Data and Control Wire Specification
Purpose
Recommended Cable
Notes
DMX In and
DMX Pass-Thru
(J10 and J6)
Belden 9729
Belden 9729 or equivalent (contact ETC
for list of equivalents). DMX is RS485 serial
and must be installed in series (i.e., daisy-
chain) topology.
Ethernet
Belden 1583A (Category 5e or better)
Install per EIA/TIA 568B. Test to TSB 67
standards. Ethernet card is factory installed
and connected to termination board at J3.
Panic In Emergency
Contact Input and
Panic Out Emergency
Indicator
(J13 and J16)
2–1.5 mm
2
(16 AWG), twisted pair
Contact input for UL 924 emergency
lighting loads and +24 VDC output for
emergency indicator.
EchoConnect
®
Station
Bus
(J17)
Belden 8471 (or equivalent) plus one
2.5 mm
2
(14 AWG) ESD ground wire
Topology-free. The total length of all
signal wiring cannot exceed 500 m
(1,640 ft).
Contact Input
(Contact Input Option
Card)
4–1 mm
2
(12–18 AWG) Class 2 wire
Maximum of 24 individual dry contact
inputs. Option card connects to
termination board at J4 or J18.
0–10V Dimming
Control
(0-10V Option Card)
4–0.25 mm
2
(12–24 AWG) Class 2 or
Class 1 wire*
Maximum of 50 ballasts (400mA) per
channel. Option card connects to
termination board at J4 or J18.
DALI
(DALI Option Card)
4–0.25 mm
2
(12–24 AWG) Class 2 or
Class 1 wire*
Maximum of 24 loops and 64 ballasts per
loop. Option card connects to termination
board at J4 or J18.
UPS Control Backup
Wiring Kit
6–0.75 mm
2
(10–8 AWG)
(copper wire solid/stranded)
SCNDRY/PRMRY
ON
OFF