Emergency Driver Power Input Wiring
51
Wall-Mount ArcLamp Emergency Driver 350 or 700
Wall-Mount ArcLamp Emergency Driver 350 and 700 have push-in terminal blocks on the
"Sense" and "Maintain" inputs. No tools are required to insert wires into the terminal block.
See
Push-In Terminal Blocks on page 20
for an illustration of the push-in terminal blocks.
•
To install wire, insert the wire into the terminal.
•
To remove wire, insert a 3.5 mm flatblade screwdriver into the tool slot next to the wire
terminal to release the wire, then pull the wire out of the terminal.
Wall-Mount
ArcLamp Emergency Driver 350/700
Sense Input Detail
Factory Wire Colors
Model
Color
Type
North
America and
Europe
green/yellow
ground/earth
North
America
black
line/hot
North
America
white
neutral
Europe
brown
live
Europe
blue
neutral
1. Make sure power is off at the main circuit breaker.
2. See
Wire and Terminal Specifications on page 16
for specification of wire size and strip
length. Prepare the wires accordingly.
3. See
Push-In Terminal Blocks on page 20
for general instructions on using the push-in
terminal blocks.
4. Insert the ground wire (typically green) into the terminal marked "Sense
."
5. Insert the neutral wire (typically white) into the terminal marked "Sense N."
6. Terminate the line (hot) wire (typically black) into theterminal marked "Sense L."
7. Tug gently on the wires to ensure they are secure.