Wall-Mount Driver Installation
23
Detail of DMX in and thru plugged into RJ45 connectors in wall-mount drivers
Wall-Mount ArcLamp Driver 150
(Wall-Mount ArcLamp Emergency Driver 150
is similar.)
Wall-Mount ArcLamp Driver 350 or 700
(Wall-Mount ArcLamp Emergency Driver 350 or
700 is similar.)
Note:
ArcLamp drivers are not self-terminating. You must terminate the last driver in
line with a DMX terminator plug in the RJ45 Thru receptacle. To purchase an RJ45
terminator, please contact your ETC customer service representative and request part
number N4086.
Eight-Pin DMX Termination
ArcLamp Driver 350 and 700 standard and emergency
models have eight-pin headers for DMX In and Thru in
addition to the RJ45 receptacles described in the previous
section.
Note:
Total length of Belden 9729 should
not exceed 500 m (1640 ft) between the
control source and the ArcLamp Driver.
Eight-Pin Connector Pinout
Pin
Description
1
ground ("Screen")
2
data -
3
data +
DMX Cable Preparation and Termination
This instruction assumes preparation of Belden 9729 (or equivalent) cable for termination to the
provided screw-terminal connector.
Note:
Not for use with Cat5, Cat5e, or Cat6 cable. When running DMX with these
cable types, use the IDC connector.