32
ArcSystem Installation Manual
Installing 100–277 V Multi-Cell Luminaires
This section provides the information needed to install 100-277 V Multi-Cell luminaires.
Supplies
The following supplies are required for installation, but not provided:
•
½ in flex conduit and conduit fittings
•
Appropriate strain relief connectors for the installation type, as needed
•
Phillips screwdriver
•
120
Ω
RJ45 terminator for DMX termination. See
Note:
Mounting hardware and installation location must support the weight of the
luminaire, conduit hardware, and all cable required for installation.
Electrical and Wiring Specification
Install ArcSystem 100–277 V luminaire on a power distribution system with reliably identified
earthed neutral and install a maximum 20 A circuit breaker on the line conductor.
ArcSystem 100–277 V luminaires and drivers accept 100–277 VAC, 50/60 Hz. ETC recommends
installing all wiring in grounded metal conduit.
Wire and Terminal Specifications
Luminaire Type
Terminal /
Connector
Conduit
Entry
Wire Range / Specification
Strip Length
Two-Cell,
Four-Cell Square,
Four-Cell Linear,
Eight-Cell
Power Input -
line/neutral/ground
½ in conduit
0.2–4 mm
(24–12 AWG)
11 mm (0.43 in)
DMX In/Thru
RJ45 Connectors
N/A
Cat5e (or better) minimum 24
AWG conductors terminated
to T568B standard
N/A
Note:
ArcSystem luminaires are not self-terminating. You must terminate the last
luminaire in line with a 120
Ω
resistor. To purchase an RJ45 terminator, please contact
your ETC customer service representative and request part number N4086.