background image

Echoflex Installation Guide

Phase Adaptive Dimmer

Phase Adaptive Dimmer (ER6CD/ER12CD)

 Page 4 of 12

Echoflex

Wiring Diagram 

Electrical Terminations 

Power to the controller is connected between the White (Neutral) and the 
Black or Brown Line power (120 or 277 VAC), respectively. The orange wire 
is an antenna. Do not cut, cap, or connect this wire. Use only UL-approved 
wire when making connections to the controller (see table below). 

Controller Interface

The controller has two LEDs and two lever-type buttons located below the 
label. 

Power LED and Learn LED

The Power and Learn LEDs can display green, blue, or red. LED color and 
combinations indicate whether the controller is providing information via 
blink codes or is in an operational mode. See 

Blink Codes and Operations

 

on 

page 6

Connection

Color

Specification

Load

Red

14 AWG, 600 V

Neutral

White

14 AWG, 600 V

Line 

Black or Brown

14 AWG, 600 V

Neutral - To other fixtures

Black - Line, 120 V or 

Brown - Line, 277 V 

White - Neutral

To other 120 V or 277 V fixtures

Green/Yellow Ground

ER12CD-AU

1200 W Dimmer

Dimmable

Lighting

Fixture

Summary of Contents for Echoflex ER12CD

Page 1: ...Electronic Low Voltage ELV and Magnetic Low Voltage MLV loads 120 V only 2 wire fluorescent ballasts and line voltage LED drivers This document covers the installation of all the Phase Adaptive Dimme...

Page 2: ...ectric shock This device utilizes high voltage and should only be installed by a qualified installer or electrician Follow all local codes for installation Before terminating the AC power wiring verif...

Page 3: ...ually cap any bare wires except the orange antenna wire The dimmer is supplied with a wire harness that is specific to the input voltage either 120 VAC or 277 VAC a Connect the striped green yellow wi...

Page 4: ...Interface The controller has two LEDs and two lever type buttons located below the label Power LED and Learn LED The Power and Learn LEDs can display green blue or red LED color and combinations indi...

Page 5: ...dicates the type and count of devices linked at pre commissioning To reset to factory default state 1 Press and hold the Clear button until the red Power and green Learn LEDs start blinking about 15 s...

Page 6: ...rt blinks that count the switches Off Occupancy sensors 2 long blinks followed by short blinks that count the sensors Off Photo sensor maximum of 1 3 long blinks followed by short blink that counts th...

Page 7: ...resistive load To change the phase dimming mode 1 Press and hold both the Learn and the Clear buttons until both the Power and Learn LEDs blink blue to access the dimming menu 2 Release both buttons...

Page 8: ...through the blink codes until 1 green blink displays disabled 4 Press and hold the Clear button until the Learn LED blinks blue to save and exit the menu To Enable LED drive mode and adjust minimum d...

Page 9: ...anual may cause harmful interference to radio communications Any modifications or changes to this product not expressly approved by Electronic Theatre Controls Inc could void the user s authority to o...

Page 10: ...Echoflex Installation Guide Phase Adaptive Dimmer Phase Adaptive Dimmer ER6CD ER12CD Page 10 of 12 Echoflex...

Page 11: ...Echoflex Installation Guide Phase Adaptive Dimmer Phase Adaptive Dimmer ER6CD ER12CD Page 11 of 12 Echoflex...

Page 12: ...Echoflex Installation Guide Phase Adaptive Dimmer Phase Adaptive Dimmer ER6CD ER12CD Page 12 of 12 Echoflex...