ETC Installation Guide

Heritage Contact Station

Unison

®

 Heritage Contact Station Installation Guide

Page 2 of 4

ETC

Wiring Requirements

The WAGO LEVER-NUTS

®

, provided in the termination kit, accepts 24-12 AWG (0.2 - 4 mm

2

) wires.

Connect Wiring

1:

Pull all required wiring (data + and data -) to the installation location. As needed, pull an additional 
ESD ground wire (required when wiring is not installed in grounded metal conduit.

Purpose

Recommended 
Wire Type

Notes

LinkConnect

Belden 8471 
(or approved equal)

LinkConnect is a bidirectional protocol that uses one pair of wires 
(data+ and data- Class 2 installation).

Auxiliary Power 
(24 Vdc)

2 each 16 AWG
(1.5 mm

2

) wires

ESD Ground

1 each 14 AWG
(2.5 mm

2

)

Required when wiring is not installed in grounded metal conduit

Contact Inputs

2 each 16 AWG 
(1.5 mm

2

) wires

Two wires are required per switch (Contact Input and Common), 
supporting up to 1,000 feet (305 m) of 16 AWG wire between the 
input and the common.

Lamp Outputs

2 each 16 AWG 
(1.5 mm

2

) wires

Two wires are required per output (Lamp Output and V out), 
supporting up to 1,000 feet (305 m) of 16 AWG wire between the 
V out and lamp output.

Note:

NEC Class 2 product to be wired in accordance to NEC Article 725 and local jurisdiction 

requirements.

N

eu

ron ID

Seri

al #

LinkConnect 
pigtail

ESD Ground 
pigtail

Auxiliary Power 
pigtail