Prepare for Installation
5
Maximum Current Draw of Enclosures
Short Circuit Current Rating (SCCR)
†Ratings are for three-phase systems.
Enclosure
Type
Phase Type
120/277 V
Maximum Current
Draw
240 V Maximum
Current Draw
AX6
Single-phase (1Ø)
120 A
–
Three-phase (3Ø)
80 A
60 A
AX12
Single-phase (1Ø)
240 A
–
Three-phase (3Ø)
160 A
120 A
AX12X
Single-phase (1Ø)
480 A
–
Three-phase (3Ø)
320 A
240 A
Enclosure Configuration
SCCR at
100-120
VAC
†
SCCR at
240-277
VAC
†
DRd6 with AX6 main circuit breaker enclosure
100,000 A
65,000 A
DRd12 with AX12X (cross-bussed) main lug enclosure
22,000 A
22,000 A
DRd12 with AX12 main circuit breaker enclosure
100,000 A
65,000 A
DRd12 with AX12X main circuit breaker enclosure
100,000 A
65,000 A