If you experience problems:
If your light is defective or develops a fault, please return it to the place where you bought it. You can call our Helpline
for advice. The Helpline will gladly give advice on any aspect of any Eterna Lighting product but may not be able to
give specific instructions regarding individual installations.
If in doubt, consult a qualified electrician.
Help line:
Tel: 01933 673 144
Fax: 01933 678 083
Email: sales@eterna-lighting.co.uk
For answers to frequently asked questions ( FAQs ) and other information visit our web-site
Lamp replacement:
>
Switch off the electricity at the mains.
>
Remove the diffuser.
>
Twist and withdraw the tube.
>
Insert new tube.
>
Restore the power and perform operation check.
>
Replace diffuser.
Replacement lamp type:
Wattage:
8 W
Type:
T5 fluorescent tube
Replacement battery type:
2.4V Ni-Cad
7030-0621
Cleaning:
>
Clean this light fitting only with a soft dry cloth—Do
not use any chemical or abrasive cleaners.
Battery replacement:
If after routine operation check, the lamp does not
remain lit for the three hour period, a new battery pack
may be required.
1) Switch off the electricity at the mains.
2) Allow batteries to fully discharge then reconnect to
supply and allow to charge for 24 hours.
3) Test again for 3 hours, if light does not remain lit
change the battery pack as follows:
4) Remove the diffuser.
5) Remove the two screws indicated on the gear tray
and open the fitting.
6) Unplug the battery lead from the circuit board.
7) Remove the two screws in the top of the gear tray
beneath the lamp that secure the battery pack in
place and lift the battery pack out of the fitting.
8) Write current date on the new battery pack.
9) Fit new battery pack securing in place using the
screws removed from the old pack.
10) Plug battery pack into circuit board.
11) Close and secure gear tray
12) Replace diffuser.
13) Restore power and allow to charge for 24 hours.
14) Perform full operation check and update test record.
Eventually, you may want to replace this light fitting:
When your light fitting and or battery pack come to the end of their life or you choose to update or
upgrade the fitting by replacing it, please do not dispose of it with your normal household waste, please
recycle where facilities exist. When you need to dispose of this fitting, check with your retailer or local
authority for suitable options. New regulations will encourage the recycling of Waste from Electrical and
Electronic Equipment ( European “WEEE Directive” effective August 2005 ).
PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING
YOUR NEW FITTING
- -
PLEASE RETAIN FOR FUTURE REFERENCE
Non-maintained emergency
bulkhead light 8W
Model(s)
YD630NM
Specification:
Power
8W
Continuous illumination
>3 hours @ 45Lm
Battery
2.4V 4.5Ah
Recharge time
~20 hours
Over-discharge protection
Yes
BLF
EBLF
30.2%
17.7%