TMCM-1310 TMCL Firmware V1.11 Manual (Rev. 1.16 / 2014-MAR-19)
93
www.trinamic.com
9.10
Status and Feedback Information
Some parameters can be read out, e.g., for visualization and feedback.
A
XIS PARAMETERS FOR READ
-
OUT
Number Axis parameter
Description
Units / Default
8
Target pos.
reached
Indicates that the actual position equals the
target position.
0/1
15
Maximum
possible current
Based on axis parameters 6 and 179 this
parameter returns the maximum possible RMS
current.
0… +3000
[mA]
16
CL velocity
reached
This flag is set when the actual velocity is
within the velocity reached window (axis
parameter 17) around the target position.
0/1
19
CL torque mode
actual current
Actual current in torque mode.
-3000… +3000
[mA]
123
CL actual current
scale factor
Actual value of the current scale factor.
0… 255
[1/256]
236
CL actual target
current scale
factor
Actual target value of the current scale factor
as defined by axis parameters 113, 114, 116,
and 117. Due to the configurable delays using
axis parameters 120 and 121, the actual target
current scale factor may be different to the
actual current scale factor.
0… 255
[1/256]
133
CL init flag
0: open loop mode or closed loop not
initialized
1: closed loop is initialized and ready for use
See also axis parameter 129.
0/1
150
Motor current
Actual motor current
[mA]
151
Current Phase A
Actual peak current Phase A
[mA]
152
Current Phase B
Actual peak current Phase B
[mA]
153
Supply Voltage
Actual value of supply voltage
[1/10 V]
154
DC Current
Actual DC current of the complete
motor
[mA]
155
Module
temperature
Actual temperature of the module
[°C]
230
Gamma
Actual field weakening value (field weakening
= speed dependent commutation angle
compensation). The read-out value can be
useful to choose values for axis parameters
108 and 109.
0… 2.147.483.647
[pps]
233
Virtual actual
position
With this parameter the actual virtual position
of the ramp generator can be read out.
−2.147.483.648…
+2.147.483.647
[µsteps]
236
CL actual target
current scale
factor
Actual target value of the current scale factor
as defined by axis parameters 113, 114, 116,
and 117. Due to the configurable delays using
axis parameters 120 and 121, the actual target
current scale factor may be different to the
actual current scale factor.
0… 255
[1/256]
237
Position error
This parameter indicates the difference
between the virtual actual position of the
ramp generator and the measured position of
the motor.
−2.147.483.648…
+2.147.483.647
[encoder steps]