background image

4

ETNA Electronic Thermal Relay displays '0.0' on the LED screen in the 
standby mode when the power is on, as shown on the left-hand side. Green 
On LED lights up when 'start' command is given by connecting start inlets 
and the LED screen displays the current value.

Password Menu 

This screen is displayed when 'set' button is pressed.
This screen requires entering the password to access the parameter setting 
menu in order to prevent unauthorized access. The password is entered using 
'Up/Down' and 'Set' buttons. Menu password is 132.

a. Error History Program

PAG program is the error history program.
After entering the correct password on the password screen, the PAG program
appears, as shown on the left-hand side. The error history program is accessed
by pressing 'Set’ and the number of the error order is selected using 'Up/Down'
buttons. Pressing 'set’ again displays the respective error code. The most recent
error is always moved to the top of the list. The program is closed by timeout.

b. High Current Limit Program

"PYA" program is the program in which the high current limit is set.
PYA program is accessed by pressing 'Up' button and then 'Set' button is 
pressed.
After adjusting the high current limit to the required value using the 'Up/Down' 
buttons, 'Set' is pressed once again to save the high current limit value. When 
the measured current is over the current limit set in this program, 'High Current 
(EYA)' failure is triggered, error LED lights up and error relay is activated.

5. Menu

Figure 2. Main Screen

Figure 3. Password Screen

Figure 4. Error History 
Program Screen

Figure 5. High Current Limit 
Program Screen

c. Low Current Limit Program

"PdA" program is the program in which the low current limit is set.
PdA program is accessed by pressing 'Up' button and then 'Set' button is 
pressed.
After adjusting the low current limit to the required value using the 'Up/Down'
buttons, 'Set' is pressed once again to save the low limit value. When the 
measured current is below the current limit set in this program, 'Low Current 
(EdA)' failure is triggered, error LED lights up and error relay is activated.

d. Number of Switches Limit Program

"PSS" program is the program in which the maximum number of switches 

allowed per hour is set. PSS program is accessed by pressing 'Up' button and 

then 'Set' button is pressed. After adjusting the number of switches to the 

requested value using the 'Up/Down' buttons, 'Set' is pressed once again to 

save the maximum number of switches allowed per hour.

An hour (60 minutes) is divided by the set value to set the time to wait between 

2 consecutive starts. For example, if PSS is set to '10' in this program, the 

minimum time between starts will be 6 minutes, so a maximum of 10 starts per 

hour are possible. The number of switches limit program should be adjusted 

according to the power of the electric motor. It can be adjusted between 0 and 

80 according to the engine power.

Figure 6. Low Current Limit 
Program Screen

Figure 7. Switch Number 
Limit Program Screen

Summary of Contents for ETR-DT

Page 1: ...Electronic Thermal Relay Product Introduction and Operation Manual...

Page 2: ...number of switches allowed per hour the delay time based on low and high current limits can be adjusted the low and high current automatic reset programs can be enabled or disabled using the menu The...

Page 3: ...he menu and save the adjusted parameters On LED Green LED lights up when ETNA electronic thermal relay is on or on relay is activated Error LED Red LED lights up along with an error code on LED displa...

Page 4: ...High Current EYA failure is triggered error LED lights up and error relay is activated 5 Menu Figure 2 Main Screen Figure 3 Password Screen Figure 4 Error History Program Screen Figure 5 High Current...

Page 5: ...s reset automatically in increasing intervals of 2 8 18 32 and 50 minutes respectively once Low Current error is triggered If low current is received at the end of the 5th automatic reset EbL error is...

Page 6: ...the password screen by pressing the Set button enter the password using the Up Down buttons and check the error history in the PAG program Manually test the current drawn by the motor check the curren...

Page 7: ...ON L N L DI 21 DI 22 N 31 32 41 42 ERROR ETR DT 0 25 A OUTPUT INPUT ON ERROR A SET START POWER OUTPUT ON RELAY OUTPUT ERROR RELAY OUTPUT ON RELAY OUTPUT ERROR RELAY OUTPUT POWER INPUT START INPUT ETR...

Page 8: ...Dudullu Organize Sanayi B lgesi 2 Cadde No 14 34775 mraniye Istanbul Turkey Tel 90 216 561 47 74 Pbx Fax 90 216 561 47 50 www etna com tr en info etna com tr Rev 06 2021...

Reviews: