14. Measuring and adjusting airflow
14.1 Adjusting the HCE and HCI Exhaust Modules
14.2 Adjusting the HCG AirGrip Module
ATTN! During measurement, HFK all Grease Filters and blind plates must be in place and the front
panel must be closed. In order to adjust airflow, the position of the adjusting plate is adjusted.
Lock the adjustment plate in place using the butterfly nuts!
Mõõteotsik
K-factor for measuring airflow
Exhaust K-factor = 16,6 (per 1 filter)
Q
v
=k√∆
pm
Airflow measuring
nozzles