Kuvamateriaali on havainnollistava
Pidätämme oikeuden muutoksiin
RDT-07-0121
37
®
NORD
fire
|
FDMB
Installation opening has to be
reinforced by profile (UW, CW).
rofil is fixed by screws ≥3,5 mm
with corresponding length.
Distance between screws
≤200 mm.
Fig. 47 Gypsum wall construction- Weichschott
EIS 90
Position:
1 Fire damper
2 Gypsum plate
3 Mineral wool (type depending on the type of construction)
4 Fire resistant board
5 Fire stop coating thickness 1 mm
6 Duct
Used materials - example:*
3 Hilti CFS-CT B 1S 140/50
4 Hilti CFS-CT
** Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system
for damper installation with equivalent material properties.
Shown schemes of incorporation and damper are illustrative only!