Kuvamateriaali on havainnollistava
Pidätämme oikeuden muutoksiin
RDT-07-0121
43
®
NORD
fire
|
FDMB
Fig. 53 Solid ceiling construction- stuffing box, fire protection mastic
EIS 60
Position:
1 Fire damper
2 Solid ceiling construction
3 Stuffing box (mineral stone wool min. density 140 kg/m³)
4 Fire protection mastic min. thickness 1 mm
5 Duct
Used materials - example:**
3 Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/50
4 Promastop - P, K, Hilti CFS-CT
*** Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing
system for damper installation with equivalent material properties.
The duct at the point of penetration can be anchored to the fire wall construction!
Shown schemes of incorporation and damper are illustrative only!