7.1 Horizontal installation
Fire dampers can be suspended by using threaded rods and a mounting profiles. Load the
suspension system depend on weight of the fire damper.
Damper assembly procedures must be done so as all load transfer from the fire separating
constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping
must be hung or supported so as all load transfer from the back-to-back piping to the damper is
absolutely excluded.
Threaded rods longer than 1,5 m require fire-resistant insulation.
Threaded rod fixing to the ceiling construction - see fig. 83
Fig. 62 Suspension- horizontal duct
Position:
1 Fire damper
2 Damping pad
3 Extension piece
4 Threaded rod
5 Mounting rail
6 Nut
7 U - Washer
8 Washer
Examples of using materials:
HILTI, SIKLA, MÜPRO etc.
Shown schemes of incorporation and damper are illustrative only!