8.1. Notes about
Important!
Ì
This device is intended to be used with a Class 2 power source in accordance with UL1310.
Ì
As an alternative an LV/C (Limited Voltage/Current) power source with the following properties can
be used:
-This device shall be used with a suitable isolating source in conjunction with a fuse in accordance
with UL248. The fuse shall be rated max. 3.3 A and be installed in the max. 30 V DC power supply
to the device in order to limit the available current to comply with the UL requirements. Please note
possibly lower connection ratings for your device (refer to the technical data).
Ì
For use and application as per the requirements of
1)
a connecting cable listed under the UL
category code CYJV2 or CYJV must be used.
1) Note on the scope of the UL approval: the devices have been tested as per the requirements of UL508 and CSA/ C22.2 no. 14 (protection against electric shock and
fire). Only for applications as per NFPA 79 (Industrial Machinery).
8.2. Safety in case of faults
Ì
The operating voltage U
B
is reverse polarity protected.
Ì
The safety outputs are short circuit-proof.
Ì
A short circuit between the safety outputs is detected on starting or when the safety outputs are activated by the device.
Ì
A short circuit in the cable can be excluded by laying the cable with protection.
8.3. Fuse protection for power supply
The power supply must be provided with fuse protection depending on the number of devices and the current required for
the outputs. The following rules apply:
Max. current consumption of an individual device I
max
I
max
= I
UB
+ I
OD
+ I
FO1A+FO1B
I
UB
= Device operating current (40 mA)
I
OD
= Load current of monitoring output (max. 50 mA)
I
FO1A+FO1B
= Load current of safety outputs FO1A + FO1B (2 x max. 150 mA)
Max. current consumption of a device chain
Σ
I
max
Σ
I
max
= I
FO1A+FO1B
+ n x (I
UB
+ I
OD
)
n = Number of connected devices