23
2121341-06-11/20 (Translation of the original operating instructions)
Operating Instructions MODULAR SAFETY CONTROL SYSTEM MSC
MSC FIELDBUS MODULES CE-...
EN
7.3. Example 3
using the test signal FI16-Test1.
During the wiring work, 24 VDC is connected to “Input1” instead of the FI16-Test1 test signal.
“Input1” has the diagnostic code 20 (Connection error).
Ì
The “I/O index” and “Diagnostic code” fields assume the following values:
1 - 20 to display the diagnosis at “Input1” of module FI16.
Figure 9:
Example diagnostics 3
In this example in Figure 10, the manual reset function on OSSD 1 is activated.
The pushbutton connected to Input1 is pressed without sending a reset command.
Ì
The “I/O index” and “Diagnostic code” fields assume the following values: 192 - 2
Ì
To indicate the diagnostics on OSSD 1A/1B (Table 8: 192 = first output).
Ì
To indicate the diagnostic code (Table 10: 2 = waiting for restart of OSSD).
Figure 10: Example diagnostics 3 with manual reset function