Operating Instructions
Electronic-Key-System EKS2
6
(translation of the original operating instructions) 2546099-01-10/21
The data structure of selection of operating mode is hierarchically structured for the individual authorization levels, and it
changes values accordingly in the individual polling levels.
MSO1
MSO3
MSO4
MSO SE
MSO2
0FF0H
3333H
33CCH
3C3CH
0F0FH
MSO1
MSO3
MSO4
MSO SE
MSO2
MSO1
MSO3
MSO4
MSO SE
MSO2
3333H
33CCH
3C3CH
0F0FH
0FF0H
33CCH
3C3CH
0F0FH
0FF0H
3333H
MSO1
MSO3
MSO4
MSO SE
MSO2
0F0FH
0FF0H
3333H
33CCH
3C3CH
Setting outputs to safe control system
Selecting operating mode
Checking selection
Confirming selected operating mode
Fig. 2:
Data structure of selection of operating mode
To fulfill the safety function of the overall
selection of operating mode
system, a suitable activation system must be connected
to the safe outputs of the device. A suitable activation system is a safe control system that can process 1-of-n signals, for
example.
The failure probability of the overall system’s safety function can therefore be calculated as follows:
PFH
D,tot.
= PFH
D,EKS2
+ PFH
D,Control
EKS2
PFH
D,EKS2
PFH
D,Control
HMI
touch panel
Access system
Activation system,
e.g. control system
Selection system
1 of n