2

Operating Instructions

2-Hand Safety Relay ESM-2H2..

Electrical connection

 

f

When the 24 V version is used, a safety transform-

er according to EN 61558-2-6 or a power supply 

unit with electrical isolation from the mains must 

be connected.

 

f

External fusing of the safety contacts must be 

provided.

 

f

A maximum length of the control lines of 1,000 m 

with a conductor cross-section of 0.75 mm² must 

not be exceeded.

 

f

The conductor cross-section must not exceed 

2.5 mm².

 

f

If the device does not function after setup, it must 

be returned to the manufacturer unopened. Open-

ing the device will void the warranty.

A1

Power supply

A2

Power supply

S11

Control line T1

S12

Control line T1

S13

Control line T1

S21

Control line T2

S22

Control line T2

S23

Control line T2

X1, X2 Feedback loop

13-14

Safety contact 1

23-24

Safety contact 2

Fig. 3:  Connections

Setup procedure

Notice

The items listed under 

Electrical connection

 must 

be observed during commissioning.

1. Wiring ESM-2H2.. to two-hand buttons:

Wire the ESM-2H2.. to the two-hand buttons as 

per Fig. 5.

2. Wiring feedback loop:

If your application provides for external contactors 

or expansion modules, connect them to the device 

according to Fig. 6.

3. Wiring power supply:

Connect the power supply to terminals 

A1

 and 

A2

 

(see Fig. 7).

Attention:

 Wiring only in de-energized state.

4. Starting the device:

Switch the operating voltage on.

5. Switching to the operating status:

Actuate the two buttons 

T1

 and 

T2

 simultaneously, 

or within 0.5 s.
The positively driven relays switch on.

6. Switching to the idle status:

Release the two buttons 

T1

 and 

T2

.

The positively driven relays switch off.

What to do in case of a fault?

Device does not switch on:

 

f

Check the wiring by comparing it to the wiring 

diagrams.

 

f

Check the two-hand buttons used for correct 

function and adjustment.

 

f

Check the operating voltage at 

A1

 and 

A2

.

 

f

Is the feedback loop closed or a jumper fitted?

Technical data

Parameter

Value

Version

ESM-2H201

ESM-2H202

ESM-2H203

Operating voltage

AC/DC 24 V

AC 115 V

AC 230 V

Rated supply frequency

50 - 60 Hz

Permissible deviation

± 10%

Power consumption

DC 24 V

AC 230 V

Approx. 1.5 W

 Approx. 3.7 VA

Control voltage at S12/S13 and S22/S23

DC 24 V

Control current (both buttons)

Approx. 2 x 40 mA

Release time of the safety relay after 

releasing a button

< 20 ms

Response delay after actuation of the 

buttons

< 20 ms

Synchronization time

< 0.5 s

Safety contacts

2 NO contacts

Max. switching voltage

AC 250 V

Breaking capacity

AC: 250 V, 1,500 VA, 6 A for ohm resistive load (6 operating cycles/minute)

250 V, 3 A for AC-15

DC: 24 V, 144 W, 6 A for ohm resistive load (6 operating cycles/minute)

24 V, 3 A, for DC-13

Minimum contact load

24 V, 20 mA

Contact fuses

10 A gG

Conductor cross-section

0.14 - 2.5 mm²

Max. length of control cable

1,000 m with 0.75 mm²

Contact material

AgSnO

2

Mech. contact life

Approx. 1 x 10

7

Test voltage

2.5 kV (control voltage/contacts)

Rated impulse withstand voltage, leakage 

paths/air gaps

4 kV (DIN VDE 0110-1)

Rated insulation voltage

250 V

Degree of protection

IP20

Temperature range

DC 24 V: -15 °C to +60 °C

AC 230 V/115 V/24 V: -15 °C to +40 °C

Degree of contamination

2 (DIN VDE 0110-1)

Overvoltage category

3 (DIN VDE 0110-1)

Weight

Approx. 230 g

Mounting

Mounting rail according to DIN EN 60715 TH35

Reliability values according to EN ISO 13849-1 for all variants of the series ESM-2H2

 1)

Load (DC-13; 24 V)

≤ 0.1 A

≤ 1 A

≤ 3 A

n

op

≤ 400,000 cycles

≤ 100,000 cycles

≤ 22,500 cycles

T

10D

20 years

Category

4

PL

e

PFH

D

1.2 x 10

-8

 1/h

1)  Additional data can be requested from the manufacturer for applications that deviate from these conditions.

Device cannot be switched on again after an 

emergency stop:

 

f

Check the two-hand buttons used for correct 

function.

 

f

Check the wiring (short circuits or similar?)

 

f

Is the feedback loop closed?

If the fault persists, perform the steps listed under 

Setup procedure

.

If these steps do not remedy the fault either, return 

the device to the manufacturer for examination.

Opening the device is impermissible and will 

void the warranty.

Maintenance

The device must be checked once per month for 

proper function and for signs of tampering and 

bypassing of the safety function. The device is 

otherwise maintenance-free, provided that it was 

installed properly.

Disposal

Pay attention to the applicable national regulations 

and laws during disposal.

EU declaration of conformity

The declaration of conformity is part of the operating 

instructions, and it is included as a separate sheet 

with the device.
The EU declaration of conformity can also be found 

at: www.euchner.com