background image

User Information 

 

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 DE-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de info@euchner.de  

Emergency Stop Safety Relay ESM-BA2.. 

V1.1.0 

Maintenance 

The  device  must  be  checked  once  per  month  for  proper 
function  and  for  signs  of  tampering  and  bypassing  of  the 
safety function.  

Techn. Data 

Operating voltage 

 

ESM-BA201 

ESM-BA202 

ESM-BA203

 

 

 

AC/DC 24V 

AC 115V  

AC 230V 

Rated supply frequency 

 

50-60Hz 

Permissible deviation 

 

+ / - 10% 

Power consumption 

 

DC 24V 

AC 230V

 

 

 

approx. 1.5W 

approx. 3.7 VA 

Control voltage at S11 

 

DC 24 V 

Control current S11...S14 

 

approx. 40 mA 

Safety contacts 

 

2 NO contacts 

Max. switching voltage 

 

AC 250 V 

Safety contact breaking capacity (13-14, 23-24   *) 

AC: 

250 V, 1500 VA, 6 A for ohmic load 

(6 switching cycles/ min)

    

 

 

 

250 V, 3 A for AC-15 

 

 

DC:   24 V, 144 W, 6 A for ohmic load 

(6 switching cycles/ min)

    

 

 

 

24 V, 3 A for DC-13 

Minimum contact load  

 

24V, 20 mA 

Contact fuses 

 

10A gG 

Line  cross section 

 

0.14 -2.5 mm

Max. length of control line 

 

1000 m with 0.75 mm

Contact material 

 

AgSnO

2

 

Contact service life 

 

mech. approx. 1 x 10

7

 

Test voltage 

 

2.5 kV (control voltage/contacts) 

Rated impulse withstand voltage, leakage path/air gap 

4 kV  (DIN VDE 0110-1) 

Rated insulation voltage 

 

250 V 

Degree of protection 

 

IP20 

Temperature range 

 

DC 24 V:  

 

-15°C to +60°C  *)  

 

 

AC 230V/115V/24V:  

-15°C to +40°C 

Degree of contamination 

 

(DIN VDE 0110-1) 

Overvoltage category 

 

(DIN VDE 0110-1) 

Weight  

 

approx. 230 g 

Mounting 

 

DIN rail according to EN 60715 TH35 

Note: 

Additional data can be requested from the manufacturer for 
applications that deviate from these conditions. 

Safety  
Characteristics  
According to  
EN ISO 13849-1  
 

The device is certified according to EN ISO 13849-1 up to a 
Performance Level of PL e. 

Device cannot be switched on again after an emergency 
stop: 

• 

Check whether the emergency stop circuit was closed 
again. 

• 

Was the start button opened before closing of the 
emergency stop circuit (with manual start)? 

• 

Is the feedback loop closed? 

If the fault still exists, perform the steps listed under 
“Commissioning Procedure”. 

If these steps do not remedy the fault either, return the 
device to the manufacturer for examination. 

Opening the device is impermissible and will void the 
warranty.  

Device does not switch on: 

• 

Check the wiring by comparing it to the wiring diagrams. 

• 

Check the safety switch used for correct function and 
adjustment. 

• 

Check whether the emergency stop circuit is closed. 

• 

Check whether the start button (with manual start) is 
closed. 

• 

Check the operating voltage at A1 and A2. 

• 

Is the feedback loop closed

What to Do in 
Case of a Fault? 

The  device  is  otherwise  maintenance  free,  provided  that  it 
was installed properly.

 

Safety characteristics according to EN ISO 13849-1 for all variants of ESM-BA2 

Load (DC-13; 24V) 

<= 0,1A 

<= 1A 

<= 3A 

T10d 

[years] 

20 

20 

20 

Category:

 

PL 

PFHd [1/h]:

 

1,2E-08 

1,2E-08 

1,2E-08 

nop

 [cycle / year]  

<= 400.000 

<= 100.000 

<= 22.500 

*) 20% Undervoltage: T

max

: 50 °C

 

Summary of Contents for ESM-BA2 Series

Page 1: ...ith electrical isolation from the mains must be connected External fusing of the safety contacts must be provided A maximum length of the control lines of 1000 meters with a line cross section of 0 75 mm2 must not be excee ded The line cross section must not exceed 2 5 mm2 If the device does not function after commissioning it must be returned to the manufacturer unopened Ope ning the device will ...

Page 2: ...et close the start button to close the safety contacts Fig 6 Monitored manual start It is monitored that the start button was opened before the emergency stop button closes Prerequisite operating voltage must not be interrupted Fig 7 Automatic start Max perm delay during closing of the safety switches on S12 and S13 S12 before S13 300 ms S13 before S12 any Warning Safety contacts switch immediatel...

Page 3: ...on 2 DIN VDE 0110 1 Overvoltage category 3 DIN VDE 0110 1 Weight approx 230 g Mounting DIN rail according to EN 60715 TH35 Note Additional data can be requested from the manufacturer for applications that deviate from these conditions Safety Characteristics According to EN ISO 13849 1 The device is certified according to EN ISO 13849 1 up to a Performance Level of PL e Device cannot be switched on...

Page 4: ...75 33 16 www euchner de info euchner de Emergency Stop Safety Relay ESM BA2 V1 1 0 Dimension Drawing Subject to technical modifications no responsibility is accepted for the accuracy of this information EUCHNER GmbH Co KG 090071 06 02 16 Translation of the Original Operating Instructions Fixed Terminals Plug In Terminals ...

Reviews: