Operating Instructions
Safety Relay with IO-Link ESM-CB
18
(Translation of the original operating instructions) 2522722-01-05/19
10. Setup
WARNING
Ì
In emergency stop applications, automatic machine startup can pose a severe danger to the oper-
ator.
-Prevent the machine from being started up again automatically by the higher-level control system.
Ì
According to EN ISO 13849-1, the manual, monitored resetting device must not trigger a machine
start.
Ì
Inductive loads can lead to welded relay contacts.
-Implement suitable, effective suppressor circuits on inductive loads.
-Connect the suppressor circuits in parallel with the load, not in parallel with the switching contact.
Ì
Magnetic fields can affect the device.
-The magnetic field strength in the surroundings must not exceed 30 A/m.
-Do not use the device near strong magnetic fields (e.g. due to transformers or magnetite).
Ì
Interference can be emitted during the operation of relay modules. Radio reception in residential
areas can be disturbed.
The device is a class-A product.
-Observe the requirements for emitted interference for electrical and electronic equipment
(EN 61000-6-4).
-Take appropriate protective measures against emitted interference.
Integrating the device description file
Ì
Integrate the suitable device description file (IODD) into the engineering tool in accordance with the number of connect-
ed BR safety switches (see chapter
).
Ì
Download the configuration to the IO-Link master.
Setting up the safety relay
Ì
Connect the power supply (24 V DC) to terminals A1/A2.
Ì
Connect the IO-Link supply L+/L- and the switching and communication cable C/Q to the corresponding port of the IO-
Link master.
¨
The PWR LED illuminates green.
¨
The IO-Link LED flashes green once IO-Link communication has been established.
Ì
Connect the sensor circuits in accordance with their wiring (see chapter
8.2. Signaling device connection variants
).
Activating the enable signal
Ì
).
Automatic start
¨
Close safety contacts 13/14 and 23/24.
¨
LED K1/K2 illuminates green.
Manual, monitored start
Ì
Press the start button.
Ì
Release the start button.
¨
Close safety contacts 13/14 and 23/24.
¨
LED K1/K2 illuminates green.
Possible diagnoses
The status information of the individual BR safety switches and the device information of the safety relay can be processed
by the cyclical data (see chapter