Operating Instructions
Safety Relay with IO-Link ESM-CB
20
(Translation of the original operating instructions) 2522722-01-05/19
12. Function test
WARNING
Loss of functional safety due to malfunction.
Ì
Proper function of the device can no longer be ensured if the function test is faulty.
-Replace the device.
1. Switch on operating voltage.
2. Close all guards.
¨
Automatic start: the machine can start.
¨
Manual start: the machine may start only after you have pressed the start button.
3. Open the guard.
¨
The machine must switch off and it must not be possible to start it as long as the guard is open.
4. Close the guard
¨
Automatic start: the machine can start.
¨
Manual start: the machine may start only after you have pressed the start button.
Repeat steps 2 … 4 separately for each guard.