15
2123622-04-06/19 (translation of the original operating instructions)
Operating Instructions Safety Systems
MGB-L..B-PN.-… (PROFINET) and With Expanded Data Structure Type C
EN
8. Mounting
WARNING
Mounting must be performed only by authorized personnel.
With two-wing hinged doors, one of the two door wings additionally must be latched mechanically.
Use a rod latch (Item) or a double-door lock (Bosch Rexroth) for this purpose, for example.
Important!
Ì
If installed flush, the switching distance changes as a function of the installation depth and the
safety guard material.
Locking
module
Locking
module
Handle
module
Handle
module
Surface mounting
Flush mounting
Operating distance
Operating distance
Tip!
Ì
You can find an animation on the mounting process at www.mgb.euchner.de.
Ì
The color and labeling of pushbuttons and indicators can be modified.
For mounting steps, see
and
.
Attach system such that operation of the mechanical release as well as inspection and maintenance are possible.
The locking screw of the mechanical release must be returned to its original position and sealed before putting into operation
(for example with sealing lacquer).