13.4. Mechanical function test
It must be possible to easily insert the bolt tongue in the locking module. To check, close safety guard several times and
actuate door handle.
If available, check function of the escape release. With active guard locking it must be possible to operate the escape release
from the inside without excessive force (approx. 40 N).
13.5. Electrical function test
1. Switch on operating voltage.
2. Close all safety guards and insert the bolt tongue into the locking module.
In case of guard locking by solenoid force
¨
activate guard locking.
Ì
The machine must not start automatically.
Ì
It must not be possible to open the safety guard.
Ì
The yellow STATE LED illuminates continuously.
3. Enable operation in the control system.
Ì
It must not be possible to deactivate guard locking as long as operation is enabled.
4. Disable operation in the control system and deactivate guard locking.
Ì
The safety guard must remain locked until there is no longer any risk of injury.
Ì
It must not be possible to start the machine as long as the guard locking is deactivated.
Ì
It must be possible to open the safety guard.
Repeat steps 2-4 for each safety guard.