Operating Instructions Safety Systems
MGB-L..B-PN.-… (PROFINET) and With Expanded Data Structure Type C
EN
13.8.5. Data block for “standard” diagnostics function
Function
Slot
Required memory in data range of the control system (IO controller)
(see below for exact bit allocation)
Diagnostics
See data sheet for slot assign
-
ment
Input range
(1 byte)
Message
Mechan-
ical life
-
-
272(6)
273(6)
272(2)
273(2)
272(1)
273(1)
274(4)
72
Bit
I0.7
I0.6
I0.5
I0.4
I0.3
I0.2
I0.1
I0.0
Output range
(1 byte)
Acknowledg-
ment
-
-
-
-
-
-
Reset
MGB
Ac-
knowl-
edg-
ment
Bit
O0.7
O0.6
O0.5
O0.4
O0.3
O0.2
O0.1
O0.0
Bit allocation
Input range
Bit
Description
Output range
Bit
Description
I0.0
Device diagnostics (PROFIsafe error #72): message present.
Diagnostic code: see table of device-specific messages.
O0.0
Device diagnostics: Acknowledge message, acknowledgment of
I0.2
,
I0.3
or
I0.4
.
I0.0
is also acknowledged if only one
message is present
I0.1
Device diagnostics, device-specific message 274(4) “Plausibility
check found an error (e.g. escape release actuated)”
O0.1
Trigger MGB locking module reset: Acknowledge message,
acknowledgment of
I1
.
I0
is also acknowledged if only one
message is present.
I0.2
Device diagnostics, device-specific message 272(1) or 273(1)
“Fault in emergency stop”
O0.2
n.c.
I0.3
Device diagnostics, device-specific message 272(2) or 273(2)
“Fault in enabling switch”
O0.3
n.c.
I0.4
Device diagnostics, device-specific message 272(3,4,5),
273(3,4,5)
“Fault in locking module”
O0.4
n.c.
I0.5
n.c.
O0.5
n.c.
I0.6
n.c.
O0.6
n.c.
I0.7
Mechanical life > 1 million operating cycles
O0.7
n.c.