11.4. Requirements for connection cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection cables.
Ì
On the usage of other connection components, the requirements in the following table apply. EU-
CHNER provides no warranty for safe function in case of failure to comply with these requirements.
Observe the following requirements with respect to the connection cables:
Parameter
Value
Unit
Conductor cross-section min.
0.13
mm²
R max.
60
Ω/km
C max.
120
nF/km
L max.
0.65
mH/km
11.5. Notes on cable laying
Lay all MGB connection cables in a common cable harness.
PLC
+ 24 V DC
cabinet
0 V
MGB-L.-...
FI1A/
FI1B
FO1A/
FO1B
UB 0V UA 0V
Important
: lay cables in a common harness
Figure 14: Stipulated cable laying