Operating Instructions
Modular Safety Control System MSC
150
(Translation of the original operating instructions) 2121331-04-04/19
9.4.7.4. MUTING "T"
The muting function is activated after the interruption of the sensors
S1 and S2 (the sequence is irrelevant) within the period defined by
the operator of between 2 s and 5 s.
The muting status ends after both sensors have been cleared.
The MUTING operator with "T" logic makes it possible to mute the
INPUT input signal via the sensor inputs S1 and S2.
¨
Prerequisite: The muting cycle can only start if S1 and S2 are "0"
(FALSE) and the input is "1" (TRUE).
Parameter
Timeout (s): Sets the time within which the muting cycle is to be ended
from 10 s to infinite. If the cycle is not complete at the end of this
time, the muting is interrupted immediately.
Figure 181: T muting
With Enable: If selected, it is possible to enable or not enable the muting function. Otherwise the muting function is always
enabled.
There are two enable modes: "Enable/Disable" and "Enable Only". On the selection of "Enable/Disable" the muting cycle
cannot be started if "Enable" is set to "1" (TRUE) or "0" (FALSE), instead it is only activated with a rising edge. To deactivate
the muting, set "Enable" to "0" (FALSE). In this mode the muting is deactivated on a falling edge, irrespective of the state.
On the selection of "Enable Only" the muting cannot be deactivated. "Enable" must be set to "0" (FALSE) to make possible a
new rising edge for the next muting cycle.
Sensor Time: The
maximum time
(between 2 s and 5 s) between the activation of two muting sensors can be set.