61
2121331-04-04/19 (Translation of the original operating instructions)
Operating Instructions
Modular Safety Control System MSC
EN
8.4.9. Module O8
MEANING
LED
RECTIFICA
TION MEASURE
RUN GREEN
IN F
AIL
RED
EXT F
AIL
RED
SEL0/1 ORANGE
ST
ATUS1/8 YELLOW
Internal err
or
OFF
Flashes 2 or 3 times
OFF
Indicates the physical addr
ess of the module
OFF
Ì
Send module to EUCHNER for r
epair
.
Compatibility err
or
OFF
Flashes 5 times
OFF
Flashes 5 times
Ì
Firmwar
e version not compatible with
MSC-CB. Send to EUCHNER for firmwar
e
upgrade.
Err
or during communi
-
cation with base unit
OFF
Flashes 5 times
OFF
OFF
Ì
Restar
t system.
Ì
If the pr
oblem persists, send module to
EUCHNER for r
epair
.
Err
or in another exten
-
sion module or MSC-CB
OFF
ON
OFF
OFF
Ì
Restar
t system.
Ì
Check which module is in the ERROR mode.
Extension module of the same type with the same addr
ess detected
OFF
Flashes 5 times
Flashes 5 times
OFF
Ì
Change addr
ess of the module (see
section NODE_SEL)
Internal node detection err
or
OFF
Flashes 3 times
OFF
Flashes 3 times
OFF
Ì
Send to EUCHNER for r
epair
.
Shor
t cir
cuit or overload
on the status outputs 1–8
OFF
OFF
ON
OFF
Flashing
Ì
Check status output connections 1–8
No supply to the status outputs 1–8
OFF
OFF
ON
OFF
Alternately flashing
Ì
Connect pin 5 to the supply
Table 54:
Tr
oubleshooting O8
Figur
e 35:
O8