background image

Accessible Toilet Alarm

N C 9 5 1   •   D E S I G N   &   I N S T A L L A T I O N   G U I D E

Approved Document No.: DNU0951001 Rev 3 • Page 1 of 8

R

ec

eption Are

as

A

cc

e ssible Toil

et

s

In

te

r view Roo

m

s

C

h

a n

g in g Roo

m

s

Single Zone Emergency Assistance Alarm

+

-

1

2

3

4

Indicators will operate: 

Intermittently when help is on the way

R

RE

ES

SE

ETT

Indicators will operate: 

Continuously when pull cord is activated

Intermittently when help is on the way

On

Calling

Call Accept

NC951

KIT CONTENTS

NC809DBBT

Accessible Toilet Reset Point c/w Sounder

Includes a ‘Reset’ button c/w braille text, red

reassurance LED and sounder.

NC807C

Ceiling Pull

Includes a red reassurance LED, red pull cord

and two triangular pull bangles.

NC949

Accessible WC

Sticker

NC943B

Single Zone Call Controller c/w Sounder

Includes a link selectable ‘Call Accept’/’Reset’

button, ‘Calling’ and power ‘On’ LEDs, 140mA PSU,

backup battery, volt-free relay output and sounder.

NC806CS

Overdoor Light c/w Sounder

Accessory Pack

Containing device

mounting screws

and shorting link.

Documentation

A Design & Installation
Guide (this document).

This equipment must be installed and maintained by a suitably skilled and technically
competent person.

This document provides a brief design and installation overview of the NC951 accessible
toilet alarm system, based on the recommendations of BS 8300 (the code of practice for the
design of buildings and their approaches to meet the needs of disabled people).

Summary of Contents for NC951

Page 1: ...iling Pull Includes a red reassurance LED red pull cord and two triangular pull bangles NC949 Accessible WC Sticker NC943B Single Zone Call Controller c w Sounder Includes a link selectable Call Accep...

Page 2: ...le gang back box TYPICAL LOCATION Inside the WC so it is reachable from the toilet and a wheelchair Position 750 1200mm above floor level and at least 350mm from corners DO NOT connect Ve to the ceili...

Page 3: ...Approved Document No DNU0951001 Rev 3 Page 3 of 8 Site the ceiling pull so its pull cord can be operated from the WC and adjacent floor area Site the call controller outside the WC in a remote staffe...

Page 4: ...ic back box is used make the earth connection to the earth terminal at connector block CONN2 If a metal back box is used the earth connection must be made to the earth bonding point on the back box Ex...

Page 5: ...the scope of BS 8300 and therefore not recommended for use in accessible toilet alarm installations However they may be suitable for use in other applications subject to the approval of the responsibl...

Page 6: ...out by pressing the reset point s RESET button EXPANDING THE SYSTEM WITH OPTIONAL EMERGENCY CALL LEVEL Up to three additional 800 Series devices any device mix can be connected to the NC943B call cont...

Page 7: ...larm call has been raised Outside the WC A member of staff accepts the alarm call by pressing the call controller s Call Accept button Outside the WC Once assistance has been provided the call is canc...

Page 8: ...nerates an alarm call when activated Indicator Red reassurance LED active in alarm IP Rating IP41 when correctly installed Mounting Surface mountable Dimensions 93mm diameter x 27mm deep NC806CS Overd...