background image

 

 

instruction and operation manual ZHK NANO 

 

 
46 / 116 

V04-18 

The control of the electric heater always takes place in such a way, that the air temperature after 
the electric heater never exceeds the permitted air temperature in the unit (40 °C, if not differently 
specified in the technical data). This item must be especially observed, when the air handling unit 
is only operated with a partial air flow (e.g. in times of reduced use of the building). 
 

 

As the heat output of an electric heater is provided very quickly and with ON-
OFF operation in the full amount, arises a significant risk of overheating the unit, 
which results in damaging several components, especially when the unit is oper-
ated with low airflows. 

 
For this purpose, the air handling is equipped with a supply air sensor, which directly measures 
and monitors the air temperature generated by the electric heater. The control engineering is used 
to ensure that the heating power of the electric heater is controlled so, that the temperature re-
mains within the permitted air temperature in the unit. 
 

Avoid overheating of AHU components by residual heat of electric heater 

In order to avoid excessive heating of components by residual heat of electric heater control en-
sures that fan motor keeps on running for at least 5 min after cut off of electric heater! By the use 
of an enabling contact (see 

Figure 87

) the control engineering also ensures, that the electric 

heater can only start its operation when the fan is running. 
 

 

If in case of main power failure (for example lightning stroke) this automatic run 
cannot be ensured, AHU may become damaged by the residual heat of electric 
heater. 

 
In order to avoid damages, an uninterrupted power supply is recommended. If AHU is not operated 
by an uninterrupted power supply after every main power failure an AHU inspection is requested 
as indicated in 

chapter 9 (Maintenance)

 

Safety concept 

Electric heater power supply is equipped with 2 contactors in serial connection! 
The 2 safety thermostats are connected such to protect the AHU both, by contactors in power sup-
ply and by software of control. In case of failure contactors must immediately cut off electric heater 
from power supply 

-

 

The 2 safety thermostats are connected in serial connection 

-

 

The 2 safety thermostats are equipped with manual reset. 

 

-

 

After triggering the reason for stopping must be detected and eliminated before reset of the 
thermostat! 

 

Thermostat 1 (Figure 84 and Figure 85) 

-

 

Position of thermostat body: fastened on electric heater at connection side, accessible by re-
moving the electric heater access panel. 

-

 Triggering 

temperature: 

pre-set 

±

 value must not be changed. 

-

 Sensor 

position: 

between heating bars. 

-

 

Function: alarm stop in case of over temperature because of low airflow. 

 

Summary of Contents for ZHK NANO

Page 1: ...1 12 16758 7 21 0 18...

Page 2: ...guide subject specific standards as well as local national and international regulations must be observed Please give this instruction manual after com pletion of the work to the operating staff of t...

Page 3: ...n the order of the insertion have to be according the filter frame raster see figure beneath Otherwise it leads to an air bypass Figure 61 filter frame for different filter sizes Figure 62 consider th...

Page 4: ...nnection has to be ensured and the transmission of vibrations and longitudinal expansion between the device and the piping system must be safely prevented In order to avoid corrosion due to water the...

Page 5: ...the heat exchanger due to mechanical force a ring is used to reinforce the copper pipe Figure 67 and Figure 68 Figure 67 copper pipe with reinforcing ring Figure 68 copper pipe with inserted reinforc...

Page 6: ...ould be carried out as shown in the scheme Figure 72 with a three way valve as a mixing valve Compared with a flow control using a straight through valve this connection avoids unequal temperature pro...

Page 7: ...ral drains may not be connected to one siphon The water from the siphon must run in a funnel Before starting fill the siphon with water In case of outdoor units an antifreeze mechanism has to be provi...

Page 8: ...ball siphons with the below shown design are included in the delivery from EUROCLIMA then the following items should be observed during installation Depending on the suction side or pressure side moun...

Page 9: ...on suction side in direction of airflow before the fan Figure 78 Suction side execution Siphon on pressure side in direction of airflow after the fan The black plug must be removed for the pressure si...

Page 10: ...ed in the scope of supply has to be installed between the device housing and the component of the duct system The aero technical connections must be executed tension and torsion free i e no forces loa...

Page 11: ...0 915 1220 2 1372 5 1830 3 1982 5 2592 5 4 2745 3202 5 5 3355 3660 6 3812 5 3965 7 Figure 81 Information on the screw distance 6 3 1 Insulation of fresh air damper Before connecting the duct section...

Page 12: ...external protective earth system has to be executed according to EN 60204 1 pt 5 2 The minimum cross sectional surface of the earth at frequency converter has to be 10 mm otherwise 4 mm at units with...

Page 13: ...witch According to the standards IEC EN 60204 and VDE 0113 all hazardous facilities have to be equipped with a main switch which separates the plant from all active conductors of the main sup ply This...

Page 14: ...s type of control decreases the lifetime of the electric heater under circumstances significantly On Off at multistage electric heater Continuous e g with suitable thyristor control Fire risk With ele...

Page 15: ...east 5 min after cut off of electric heater By the use of an enabling contact see Figure 87 the control engineering also ensures that the electric heater can only start its operation when the fan is r...

Page 16: ...riggering temperature set to 70 C value must not be changed Sensor position downstream of electric heater in upper area of airflow Function alarm stop in case of over temperature because of missing ai...

Page 17: ...nt of the supply air volume flow 7 6 Lighting Depending on the number of delivered optional lamps the assignment of the switches and junction boxes can be found below 1 Lamp 1 switch 1 4 Lamp 1 switch...

Page 18: ...tools etc and documentation from the unit Such parts can be sucked in by the fan and lead to its destruction check all bolt connections and electrical connections and retighten if necessary Ensure th...

Page 19: ...d diff pressure Pa Sw Measured diff pressure Pa V Air density at the fan kg m If several fans in a fan section are operated in parallel with the same speed then the total airflow rate is accordingly a...

Reviews: