Instruction Manual ZHK
122/129
V07-19.0
11.3.4
Air filters
-
Only use electrostatic deductive filter.
-
Use original spare parts.
-
For filter types that are equipped with potential equalization cable, each filter cell must be con-
nected to the potential equalization with the AHU in the fixed-mounted metal filter frame using
self-tapping screws or bolts.
-
To prevent the formation of an explosive atmosphere by stirring up of dust deposits, the equip-
ment has protective systems and components designed to avoid deposits of combustible dusts
as far as possible. Therefore, for all components corresponding service openings are provided.
-
Periodically the AHU shall be cleaned (depending on the amount of dust) to remove all dust and
debris.
11.3.5
Heat exchangers / steam humidifiers
The heat exchange medium temperature and the steam humidifier surface tem-
perature specified in the data sheet shall not be exceeded. Otherwise, the speci-
fied temperature class is no longer valid -
danger of explosion!
-and the decla-
ration of conformity loses its validity.
11.3.6
Field devices
On site assembled field devices must comply the ATEX class specified by EUROCLIMA.
-
The electrical components (switches, lights, sensors, motors, etc.) must be approved for opera-
tion in explosive atmospheres and must be equipped with an appropriate marking.
-
The cabling must meet the relevant standards.
-
Appropriate potential equalization has to be prepared.
-
Outdoor AHUs must be equipped with a professional lightning protection system and all metal
parts have to be connected to the ground conductors.
-
For indoor AHUs all electrically conductive parts must be protected with a professional grounding
measure (potential equalization). By derivation of lightning currents, this measure prevents the
formation of ignition sources.
-
Pipelines must be considered as a potential ignition source, since their temperature can rise up
to 110 °C.
11.3.7
Declaration of conformity
The declaration of conformity to ATEX applies only to the original delivery AHU and with proper
repair and maintenance. When changes on the AHU are made, which are not agreed in writing, the
declaration of conformity loses its validity.