a) items 7 to 9
b) item 10, implementation of emergency stop function in control system
ZHK-AHU without EUROCLIMA-control
-
The specified main switch must be provided by of the client
-
Is to carry out independent from EUROCLIMA supply of main switch for fan motor. Fan motor
main switch cuts just the motor off.
-
Furthermore, on responsibility of the client must be ensured that all items 1 to 10 of the above
specified
Requirements according to DIN VDE 0660 and IEC 947-3 on a main switch in
RED-YELLOW execution
are fulfilled
7.5
Variable, frequency-controlled drives (VFD, frequency converters)
If the frequency converter is supplied from someone else than EUROCLIMA, please note the fol-
lowing points to ensure proper operation:
-
Suitability for fans with variable torque.
-
The frequency converters supplied by EUROCLIMA are usually equipped with interference fil-
ters. The interference filter must be compatible with the on-site power supply system.
-
The current output of the frequency converter must be compatible with the nominal motor ca-
pacity.
-
The frequency converter must be adapted for the installation type (IP rating, type of ventilation,
temperature, electromagnetic environment ...)
-
If the frequency converter will be mounted in the fan section, the frequency converter must be
equipped with a separate display unit.
In this case, the display is to be kept on the outside of the AHU - operating in the
fan section is not permitted for safety reasons!
When using residual current devices (RCD), the supply cable has to be equipped with a RCD,
which is approved for frequency converter (Type B or U, 300 mA).
Plug fans
When using this type of fan (fan with direct-coupled motor-wheel), a frequency converter is neces-
sary to reach the operating point.
7.6
Electric heaters
An electric heater is designed to heat the airflow, which is stated on the technical data sheet, from
the specified air inlet temperature to the air outlet temperature. EUROCLIMA provides electric
heaters with one or more stages according to customer requirements.
The control of the electric heater provided by the customer can be carried out in several ways:
-
On-Off at single-stage electric heater (this type of control decreases the lifetime of the electric
heater under circumstances significantly)
-
On-Off at multistage electric heater
-
Continuous (e.g. with suitable thyristor control)