Instruction Manual ZHK
V07-19.0
105/129
Figure 204:
Adjustment of pullies
Pulley diameter d
d1
, d
d2
in mm
Max. distance x
1
, x
2
in mm
< 112
0,5
< 224
1
< 450
2
< 630
3
Table 16:
Maximum deviation at adjustment of pulleys
For quick results during the pulley alignment for factory mounted pullies, we recommend setting
the same protruding thread size of the threaded rods on the left and right side shown in
Figure 205:
Adjustment of pulleys via threaded rods
In case of various pulley widths, the gap must be equal on both sides.
The belt drive is to be re-tensioned, after the first 10 operating hours.
Belt tension
The correct tension of the belt is obtained through adjustment in compliance with the tensioning
data, which is calculated separately for each drive. The necessary information to tension new and
used belts can be found on the tensioning data sheet, which see sample in