Instruction Manual ZHK
50/129
V07-19.0
Figure 98:
Door
‚
open
’
Figure 99:
Door
‚
closed
’
, not
,
locked
’
Doors which allow access to the fan section
-
are equipped with a door lock.
shows the lock in the position 'locked', locking slit is
in vertical position.
-
offer a physical barrier as a protection against the danger zone
-
stay securely in position and can be opened only by using a key
-
during the operation do not permit access to the fan section
The keys are provided attached to the handle, refer to
Figure 100:
Door
‚
closed
’
and
‚
locked
’
Figure 101:
Delivery of the keys
Abovementioned doors with locks are an effective safety device according to EN ISO 12499: there
is no situation where entering during fan operation is required, refer also to
chapter 2.2 (Indica-
tions for minimizing specific hazards)
.
The locking mechanism of the hinged door is on the inside of the door panel and is shown in
(closed position) and
(open position). The rolling piston can be pressed from
above (if you are in the AHU) with your thumb in the position 'open'. Thereby, for example, an acci-
dentally trapped person is able to open the locked door from the inside of the AHU.
Figure 102:
‚
Closed
’
Figure 103:
‚
Open
’
not locked
locked