Ensure, that the free distance between the two ends of the rigid (grey) tubes is not less than
20 mm and not more than 60 mm according the drawing.
-
Ensure that the (black) flexible tube covers the (grey) rigid tube ends at each side for a length
of 60 mm according to the drawing.
-
Mark the correct position of the flexible tube on the rigid tube (60 mm length) before installing
the flexible tube.
2. Install the flexible tube and clamps
-
Clean the plastic tubes and flexible connector tube carefully with a dry and clean cloth
-
Check to use the
correct clamps: The clamps are imprinted with “NORMA” and the size range
must be as indicated in
Do not apply any lubricant between the black flexible tube and the rigid (grey)
tube. This could degrade the flexible rubber tube and reduce the safety of the
connection.
Do not use any cleanser of benzene, this could damage the rubber material.
3. Positioning of the flexible tube and clamps
-
Check if the flexible tube is positioned correctly overlapping 60 mm on each end the grey rigid
-
Firstly, install loosely the indicated type and number of clamps on each side of the connection.
-
Check if the clamps are positioned on each side completely within the 60 mm overlapping
length.
4. Fixing of the clamps
-
Tighten the clamps using a torque wrench. Fix the screw with a torque of 5 … 6,5 Nm.
Figure 158:
Correct positioning of the flexible connecting tube
(black); dimensions in mm