Crisis EVC Network Expander Installation Guide
Page 21
www.eurofyre.co.uk
9 Technical Specification
Power Supply & Charger
Power Supply & Charger
AC Input
AC Input
/- 10%, 50/60Hz
/- 10%, 50/60Hz
Internal Power Supply
Internal Power Supply
12Vdc Nominal
12Vdc Nominal
Supply and Battery
Supply and Battery
Monitored Open, Short, Fuses
Monitored Open, Short, Fuses
Protection
Protection
Deep Discharge, Short, Thermals
Deep Discharge, Short, Thermals
Temperature Compensation
Temperature Compensation
Yes
Yes
Battery Information
Battery Information
1 x 12V 7Ah VRSLA
1 x 12V 7Ah VRSLA
Mains Fuse
Mains Fuse
1A HRC(T)
1A HRC(T)
Battery Fuse
Battery Fuse
Self Resetting PTC
Self Resetting PTC
Max Charge Current
Max Charge Current
500mA
500mA
Table 4: Power Supply & Charger Technical Specification
Inputs
Lines
8
Remote Enable
Short to Use
End of Line Monitoring
10KΩ 0.6W Resistor
Table 5 Inputs Technical Specification
Relay Outputs
Number and Type
Fault and In Use, Volt Free 30Vdc 1A
Table 6: Relay Outputs Technical Specification
Controls
Number and Type
None
Table 7: Controls Technical Specification
Indication
Number and Type
3 x PSU Status Indicators
1 x CPU Fault Indicators
1 x General Fault Indicator
1 x RGB Mode Indicator
8 x RGB Line Indicators
Table 8: Indication Technical Specification
Enclosure
Enclosure
Back Box Finish
Back Box Finish
RAL 7035 Grey
RAL 7035 Grey
Dimensions (W x H x D)
Dimensions (W x H x D)
220mm x 300mm x 95mm
220mm x 300mm x 95mm
Entries
Entries
14 x Knockouts Top, 2 x Rear Slots
14 x Knockouts Top, 2 x Rear Slots
Flush Cut Out
Flush Cut Out
225mm x 305mm x 85mm
225mm x 305mm x 85mm
Table 9: Enclosure Technical Specification