Short Circuit Fault
If the fault is a short circuit fault, then the S/C LED will be flashing. This S/C LED will be flashing for S/C faults on the zone and sounder circuits. It
can take up to 60 seconds from repairing a fault for the display to clear.
Figure 5: Short circuit fault indications
Power Supply Fault
The power supply fault light flashes when the mains supply has failed or the standby batteries or its charger is faulty. If the mains supply fails,
the panel will only operate for the standby period dictated by the size of the batteries fitted. If the batteries or charger fails at the same time as
the mains, the panel will be inoperative.
Figure 6: Power supply fault indications
System Fault
The System Fault LED and General fault lights when the panel’s micro-processor has Reset, typically after excessive electrical interference, or
if the contents of its memory have been corrupted. This fault can only be cleared by turning the key switch from off position to control enable
position and then back to the off position again. If the fault re-occurs within two minutes, this is indicative of a corrupt memory and expert advice
should be sought.
Figure 7: System fault indications