5 Panel Indications & Controls
Figure 1: Panel indications and controls
Two levels of control are available to the User(s) of this Fire Alarm Panel.
5.1 General Controls
When the Panel is in its normal state, the indicator lights on the front of the enclosure give a comprehensive overview of the system’s current
status. Any fire and fault conditions are clearly displayed, and any disablements highlighted. For detailed descriptions of what each indicator
means, please refer to the table on the 5.3 Summary of LED Combinations and their Meaning.
The only functions that can be performed by the user when the panel is in its normal state are:
•
Overriding any delays, which may have been programmed into the panel by pressing
•
Putting the panel into the accessed state – see below.
5.2 Accessed Control (available to authorised users only)
To avoid unauthorised changes to critical parts of the fire alarm system, controls such as silencing the sounders, resetting an alarm condition and
implementing disablements are only accessible via a secure method of entry which puts the panel into the accessed state.
To put the panel into the accessed state:
Enter the access code (1245) then press
. To exit accessed state press
three times. If the wrong code is entered three times,
then the LED display will light a combination of LED’s. If this happens you will need to contact Eurofyre Limited for the code.
Changing the access code
1.
Enter the current access code and press
(Control Enable lit)
2. Press
for 3 seconds panel will beep
3.
Re-type the access code and press
4.
Type the new code
5. Press
for 5 seconds
6. The will give a confirmation beep. New code is active
Information on how to use the accessed control can be found on pages 14-17
of this User Manual.
5.3 Summary of LED Combinations and their Meaning
Use the table below to determine the condition of the panel.
LEDs Lit
LED Condition
Panel Status
POWER
Constant Green
The panel is supplied with power, and has no faults/fires (System Normal)
GENERAL FAULT
Flashing Yellow
GENERAL FAULT
SUPPLY FAULT
Flashing Yellow
Flashing Yellow
There is a problem with either the mains supply or the battery backup (consult Installation
manual for details of flash meanings).
GENERAL FAULT
EARTH FAULT
Flashing Yellow
Constant Yellow
There is a wiring problem. One of the cables is touching the earth screen.
GENERAL FAULT
ZONE FAULT
Constant Yellow
Flashing Yellow
There is an open circuit fault in the wiring of the zone indicated.